|
Geotechnical Investigations For Corrosive Soils BY G. Clark Davenport, Edward E.
Rinne, and Alfonso Maldonado Zamora
INTRODUCTION
It is always a pleasant surprise to
find remnants of past civilizations, be they large
unexplored ruins or small objects such as
projectile-points. All such remnants share a common
factor in that they have been and are subjected to
corrosion processes. These processes are the result of
wind, rain, soil burial and electrochemical processes.
Two interesting cases relating
archaeological remnants to cathodic protection are
presented in reference 5. The first case concerns the
discovery of iron objects which were buried in corrosive
soil, yet these objects exhibited a high state of
preservation. The preservation, in this case, was
directly related to the fact that the objects
constituted part of a human burial, which also included
leather items and bones. The leather items produced
tannates which impede the growth of sulfate-reducing
bacteria. The bones (animal and human) produced
phosphates, which in turn, through a complex chemical
action, formed a protective film around the iron
objects. The second case involved the finding of a
Viking sword that was buried with a warrior. As was
fairly customary during the Viking Age, a warrior’s
armament and equipment were "killed" prior to burial.
The sword in this case was bent, as a method of
"killing." When found, the sword exhibited corrosion
only localized around the bend, the area of maximum
stress. The rest of the sword was well preserved. This
phenomena relates to stress corrosion.
Although unplanned, both the above
cases illustrate corrosion protection processes.
Corrosion of buried metallic objects, such as
underground piping, is associated with both the flow of
electricity and the chemical processes within the soils
surrounding the objects. Twenty to thirty years ago an
accepted and often used method of corrosion protection
for buried pipeline was to increase the wall thickness
of the piping. This simply had the effect of adding time
to the corrosion process and extending the life of the
pipeline. Since that time, more economical and efficient
corrosion control methods have been developed.
The control of external corrosion
on buried metallic objects is now generally achieved by
a combination of one or more complementary procedures of
coating, backfilling and cathodic protection.
Geotechnical investigations play a very important role
in determining some of the design parameters for
cathodic protection systems.
BASIC PRINCIPLES
The type of electrical circuitry
which sustains corrosion processes in soils, for example
on a pipeline, is a function of differing soil
properties along the route of the pipeline, relationship
of the pipe to other metallic objects in the same soils
and the type of metal used in the connections on the
pipe route. This flow of electricity is associated with
an electrochemical process which can cause corrosion
products, such as
rust, on the metallic surface which
is discharging the electrical current. The flow of
electricity being discharged from one metallic surface,
termed the anode, is completed by the passage of the
current from the electrolyte (in this case the soil) to
the same or other metal objects nearby. The metallic
object receiving the electrical current is termed a
cathode. The total amount of metal removed from the pipe
in the corrosion process is directly related to the
amount of electricity flowing in the completed circuit.
CATHODIC PROTECTION
Cathodic protection is a process in
which an electric current is forced to flow from an
auxiliary anode into the structure to be protected
against corrosion, thus making the entire structure a
cathode. Cathodic protection, if necessary, is normally
applied to properly coated structures to minimize the
cost of the total corrosion control system.
In practical terms cathodic
protection may be applied by the use of sacrificial
anodes or power impressed groundbeds.
Sacrificial anodes are manufactured
of materials which are more noble in the electromotive
series and would corrode preferentially when connected
to mild steel or cast iron. Such anodes, generally cast
of magnesium, aluminum or zinc, are installed alongside
the pipelines in the trench line at intervals determined
by design and connected to the pipelines via a test post
facility.
Power impressed systems comprise an
a.c. powered transformer-rectifier which provides a
controllable d.c. output. The positive terminal is
connected via a single core cable to a groundbed
consisting of high silicon iron or graphite anodes laid
in a trench or borehole located generally 50 to 150
meters from the structure to be protected.
When current is supplied, the anode
will discharge electrical current into the ground, the
underground structure will receive the discharged
current, thus protecting the structure from corrosion.
These systems can become very complex, requiring careful
design and construction.
In order to properly design
cathodic protection systems, preconstruction analysis of
the following factors is necessary:
-
The type, grade, length and
size of the piping to be used will determine the
electrochemical reaction processes that will take
place when the pipe is placed in soils of differing
electrical characteristics.
-
A knowledge of the anticipated
life of the piping will give an insight into the
type, and hence expense of the cathodic protection
system most suitable for use.
-
The electrical properties of
the soils along the pipeline route are analyzed to
provide information on the type of electrical
reaction that may take place between the pipe and
the adjacent soils. As an example, the lower the
soil resistivity, the higher the current that will
flow from the pipe into the soil.
-
The chemical and
bacteriological characteristics of the soils along
the piping route are analyzed to determine the type
of electrochemical reaction that may take place and
to determine the type of oxidation process that may
exist. Oxidation processes may promote corrosion.
-
The types of available
materials applied as coatings to pipelines form an
essential criterion to the design of a cathodic
protection system. Generally, cathodic protection
requirements may be reduced when a high quality
coating is achieved.
-
Details of other corrosion
control practices within the immediate area of
construction should be investigated. This is
necessary so that a compatible cathodic protection
system can be designed for newer structures.
-
Existing facilities within the
immediate area of construction should be
investigated in order that suitable precautions may
be taken to design compatible cathodic protection
systems and to provide information on stray
currents.
-
In order to maintain cathodic
protection levels, the buried structure or pipe must
be electrically isolated from all other metalwork.
Analysis of pipeline connections to other structures
will provide information relating to the electrical
isolation procedures that would be necessary prior
to the application of cathodic protection.
Cathodic protection is a surface
protection only, and if installed for the external
surface will have no effect on internal corrosion. The
control of internal corrosion cannot always be readily
achieved. For large diameter pipes, internal coatings
can be readily applied and inspected. However, the
internal coating of small diameter pipes (less
than.50-75 millimeters) is particularly difficult from a
practical viewpoint and inspection cannot easily be
performed. A discontinuous coating may lead to localized
corrosion, creating a worse situation than having no
applied coating.
Where internal corrosive conditions
are anticipated, a corrosion monitoring system may be
used where test "coupons" are installed within the pipe
and regularly inspected to evaluate the corrosion rate.
COATINGS AND BACKFILL
Although these are not cathodic
protection procedures, they are complimentary to
cathodic protection systems. The use of coatings and
backfill will only be mentioned briefly, as they were
not considered in detail for the case history to be
discussed.
The use of pipe coatings or
wrappings reduces the area of the underground structure
exposed to the electrolyte (soil),
hence reducing corrosion. Coatings
may take the form of paints, greases, bitumen, or coal
tar, which may be reinforced with fibrous material and
epoxy resins. Wrappings consist of protective materials
in the form of plastic sheets or tapes. All coatings and
wrappings should have a high electrical resistance,
should resist abrasion and should be alkali resistant in
certain types of soils. When applied to underground
structures, coatings and wrappings should adhere
strongly to the surfaces to be protected, should exhibit
no blisters and should be applied in continuous form
such that no gaps are left on the structural surface.
Coatings may be applied to the metallic structure either
prior to or upon arrival at site. It is preferable that
the trench backfill materials are chemically inert, for
instance, washed sand, but economic and availability
constraints at construction sites may preclude its use.
MEASUREMENT OF EARTH RESISTIVITY
The common factor that appears to
relate soils to the corrosion processes is the
resistivity of the soils. Measurement of soil
resistivity is therefore a prime concern in cathodic
protection considerations.
In electrical resistivity
surveying, the most common method used to measure earth
resistivity is to drive a current through the ground
using galvanic contacts. Normally a four electrode
system is used, driving the current through two of the
electrodes and measuring the established potential in
the earth with the other two electrodes. The four
electrode system offers an advantage over a two
electrode system in that resistivity measurements are
heavily affected by the properties of the soils close to
the electrodes, and the use of four electrodes reduces
this effect.
The choice of electrode
configuration is governed by the type of investigation
desired. In studying the lateral variations in
resistivity across a site, a fixed electrode separation
is used and maintained, and the whole electrode array is
moved along a line of profile. This electrode
configuration is termed the Wenner array. In studying
the vertical variations of resistivity with depth, the
spacings between the electrodes are gradually increased,
which enhances the effects of materials at depth with
larger electrode spacings. This latter electrode
configuration is termed the Schlumberger array.
Normally, soil resistivity surveys
for cathodic protection studies are performed using the
Wenner configuration. The Schlumberger array offers
advantages over the Wenner array in that the former is
more convenient from an operational point of view, local
inhomogeneities close to the potential electrodes can be
rapidly located on the apparent resistivity curves and
the theoretical computation or the apparent resistivity
curves can be performed more rapidly and with less
assumptions than similar computations for the Wenner
array. The Schlumberger array does not provide for
detailed information on lateral changes in the
resistivity values across a site. A schematic of the
Schlumberger array is shown on Figure 1. The use of this
type of array produces a vertical electrical sounding (VES).
For the specific case history to be
discussed, the site was one of eleven fairly large sites
to be investigated within a rigid time schedule. Most of
the sites investigated were large enough to prohibit the
use of the Wenner array due to the excessive amount of
time that would be required. Therefore the Schlumberger
array was selected for use in the field investigations.
With the spacings used between successive vertical
electrical soundings, lateral changes in soil
resistivity across each of the sites can be measured
with sufficient detail for the purposes of a cathodic
protection investigation.
EQUIPMENT
Instrumentation for most electrical
resistivity surveying is relatively simple. Current is
normally provided by dry batteries in the form of a
single long direct-current surge. The current electrodes
(A, B) are normally steel or copper-clad steel stakes
driven into the ground. Frequently in dry areas, the
soil around the electrodes may have to be moistened to
insure proper contact with the ground.
The voltage between the potential
electrodes (M, N), which are also made of steel or
copper-clad steel, is measured with a
potentiometer or a voltmeter.
Contact with the soil of the potential electrodes is not
as important as with the current electrodes.
The equipment selected for this
investigation consisted of a dry battery unit capable of
voltage outputs from 50-400 volts DC, an amperimetric
unit capable of measuring current intensity from 300
millamps to 3 Amps (with 1 percent accuracy), and a
millivoltmeter capable of measuring voltages from +1
millivolt to +100 volts at an accuracy of 1 percent.
This equipment was supplemented by using steel
electrodes, and lightweight, well insulated copper
cables to connect all systems to the array. Spacings
used for this investigation are shown on Figure 1.
INTERPRETATION OF MEASUREMENTS
In the Schlumberger array, the
depth to which the resistivity is averaged is roughly
equal to half the separation between the current
electrodes. This resistivity is computed using the
formula:
p = p (L2) (deltaV)
(2l) (I)
where L = the half-separation
between the current electrodes (A, B) measured in
meters;
l = the half separation between the
measuring electrodes (M, N) in meters;
AV = the voltage at the measuring
electrodes, in volts;
I = the current between the current
electrodes, in amperes.
This formula is based on the
assumption that the ratio V/l is approximately equal to
the voltage gradient, E, at the center of the electrode
array.
The resistivity as calculated from
the above equation is not necessarily equal to the
resistivity of the portion of the earth over which the
measurement was made, due to the influence of the
electrical properties of one layer on another layer. For
this reason the value obtained from the above equation
is termed the apparent resistivity. The interpretational
process consists of deducing a likely set of true
resistivity values which would be compatible with the
observed apparent resistivity values. In many cases,
there exists no single set of true resistivities that
correspond to a particular set of apparent resistivities,
and as such, the true resistivity cannot be uniquely
determined.
The apparent resistivity which
would be measured over a series of uniform horizontal
layers presents a fairly simple case, and since this is
frequently a good first approximation to gelogic
conditions, the first step in the interpretation process
normally involves determining what layer thicknesses and
resistivities can explain the measured apparent
resistivities.
Numerous investigations have
produced resistivity curves for various geologic
conditions using theoretical data. These curves have
been plotted in terms of dimensionless variables and
form the basis for the curve-matching technique of
resistivity interpretation.
A curve of the field data, in which
the values of the observed apparent resistivity are
plotted against electrode spacing on logarithmic graph
paper, will have the same shape as the theoretical
curves plotted in terms of dimensionless variables. By
plotting the field data on graph paper of the same scale
as the theoretical curves, the field data curve may be
laid over the theoretical curves. The field curve is
moved until the field points correspond or match with
the points of the theoretical curves. The only
requirement is that both sets of curve axes must be kept
parallel. The depths and corresponding true
resistivities are then read off of the field matched
theoretical curve. It must be remembered, however, that
there are available many differing sets of theoretical
curves for many types of geologic settings and the curve
matching process may become time consuming.
LABORATORY TESTING
Since corrosion
processes are electrochemical in nature, it is advisable
to perform chemical analyses of soil samples from the
vicinity of a proposed buried object. Soil acidity (pH)
should also be determined, as this can be related to the
corrosion potentials of soils. Finally, if possible,
groundwater samples should also be analyzed.
Laboratory values of electrical
resistivity in soil samples can play a very important
role in determining cathodic protection design
parameters. For example, dry soils that may be
periodically subjected to irrigational water may be
enhanced in their corrosion potential. It may be very
difficult to study this effect in the field, as it may
be impractical to saturate the on-site materials. This
effect, that of enhanced soil corrosion potential as a
function of saturation, can be practically studied in
the laboratory.
Bulk soil samples can be obtained
of on-site materials. In-situ densities and moisture
contents should also be determined at the same time the
sample is obtained.. The bulk sample can then be
compacted to its natural density and moisture content in
a specially designed tube. The tube is designed to allow
for resistivity determinations. The authors chose to use
a tube made of PVC, as diagramed on Figure 2. The tube
and soil sample, after the determination of the dry
apparent resistivity, are then soaked in water for 24
hours. The apparent resistivity on the saturated soil
sample is then determined.
CASE HISTORY
INTRODUCTION
A geotechnical investigation was
conducted on eleven sites, scattered throughout the
Kingdom of Saudi Arabia, to assess soil corrosivity and
the need for cathodic protection at each of the sites.
Proposed construction at each of the sites called for
the use of underground utility piping. At most of the
sites, this piping would be subject to irrigational
waters, and hence at each site the potential corrosivity
had to be assessed for both dry and saturated soils.
For the purpose of this case
history, results from such an investigation are
presented from two adjacent sites, near the city of
Jeddah. On-site investigations consisted of electrical
resistivity surveying, collection of bulk soil samples
for laboratory analysis and in-situ density measurements
at each soil sample site. Two water samples were
collected, one from each site, but in transit outside of
the Kingdom, for analysis, the sample containers were
broken, and hence no analysis was performed.
The electrical resistivity surveys
were performed using the Schlumberger array. The
electrode spacings were chosen such that a theoretical
interpretation of the electrical resistivity values
could be made to a depth of 10 meters. This depth was
approximate in that it depended on the electrical
properties and characteristics of the site materials.
The depth of 10 meters was considered to be a realistic
maximum depth for the proposed utility piping.
The field work took
a total of four days, during which time 40 vertical
electrical soundings were completed and three soil
samples were obtained. The results of each vertical
electrical sounding were interpreted in the field, such
that errors could quickly be corrected and anomalous
conditions could be checked on site.
SITE DESCRIPTION
The total site for the proposed
construction activities consisted of an area of
approximately three kilometers by one kilometer. Within
this area, the geotechnical investigation was conducted
on two smaller areas, approximately one kilometer by one
kilometer, and one kilometer by two kilometers in size.
There were no existing permanent facilities or
underground piping in either of these areas at the time
of the geotechnical investigation.
A general site and vertical
electrical sounding location map is shown on Figure 3.
The site was located adjacent to the Red Sea. A detailed
knowledge of the groundwater system was unknown;
however, it was assumed that the groundwater was highly
saline. On-site personnel mentioned that after periodic
rainstorms, the groundwater system was noted to rise
40-60 centimeters. This rise was believed due to
capillary action.
Site soils information was
available from a soils investigation conducted prior to
the geotechnical investigation. The original surface
soils consisted of loose silty sands mixed with some
gravels. In lower areas, the sands exhibited some
cohesion due to cementing materials. Throughout the
site, the sand material was leveled and fill material
was placed over it to bring the site to construction
grades. There were approximately two meters of fill
material which consisted of dune sand throughout the
site. The fill material and original surface soils were
underlain by fragmented limestones and corals.
EVALUATION CRITERIA
The exact size and nature of the
proposed underground utilities for this site were not
known; therefore for the purposes of this investigation
it was assumed that the categories of buried materials
which would be subjected to corrosion or deterioration
would generally be as follows:
-
cast or ductile iron water
mains;
-
black steel chilled water air
conditioning lines;
-
raw water lines and tanks
(concrete);
-
thermal piping;
-
black steel POL lines and
tanks;
-
assorted ferrous metal
structures.
The deterioration effects of
plastic piping were not investigated.
For the purposes of evaluating the
corrosive electrical properties of the soil in regard to
the buried structures the following criteria were
adopted:
Soil Resistivity
-
50 - 100 ohm-meter mildly
corrosive
-
30 - 50 ohm-meter moderately
corrosive
-
below 30 ohm-meter very
corrosive
It should be noted that wide
variations in soil resistivities within a site or over
the surface of a continuous structure can cause the
formation of corrosion cells.
The resistivity readings used for
the evaluation of the site data were taken on an average
of those values between depths of one meter to five
meters. In preparing recommendations for the necessity
of cathodic or other protection, it was assumed that the
utility services would not be buried deeper than three
meters.
RESULTS
The resistivity readings are
tabulated on Figures 4 to 7.
These readings averaged for a depth
of 3 meters can be summarized as follows:
|
Readings |
Number of Soundings |
|
Above 100 ohm-meter |
0 |
|
Between 100-5- ohm-meter |
0 |
|
Between 50-30 ohm-meter |
0 |
|
Below 30 ohm-meter |
40 |
The results of the electrical and
chemical analyses of the soil samples are presented on
Table 1.
A lack of correlation was noted
between the dry resistivity values as determined in the
field and in the laboratory. The probable reason for
this lack of correlation was the change in internal
structure and soil-water system of a partially saturated
soil between its in-situ and recompacted state. This
change was significant even though the recompacted
laboratory specimens were compacted to the in-situ water
content and unit weight.
For this reason, the dry
resistivity values as determined in the laboratory were
often erratic or unobtainable.
Vertical electrical soundings were
performed in.wet soils on the sites where possible.
Laboratory resistivity values for saturated samples in
the same soils correlated well to the resistivity values
determined in the field. In a fully saturated state the
soil-water system is more closely reproduced, i.e., the
amount of interstitial water in a laboratory sample is
very close to the amount of interstitial water in a
fully saturated in-situ sample.
RECOMMENDATIONS
From these results it was apparent
that any underground metallic piping or structures on
this site would be subjected to a corrosive environment.
It was recommended that cathodic protection should be
installed with any such piping or structures.
Once the characteristics of the
underground piping or structures have been selected,
specific cathodic protection design recommendations
could be made from the results of this investigation.
The soil pH in this area did not
indicate soil acidity to be a corrosion factor.
The soil had a high sulfate content
and this would have to be considered when specifying
materials which are to be buried. This might apply in
the case of concrete or asbestos-cement.
ACKNOWLEDGEMENTS
The authors wish to acknowledge the
United States Army Corps of Engineers, U.S. Army
Engineer Division, Middle East for their assistance and
support during the course of the geotechnical
investigation. we also wish to thank the same group and
Dames & Moore for their permission and encouragement in
the sharing of the principles and results of the
investigation.
Table 1
Soil Analyses --JEDDAH
|
Sample Number: 1
Location: Vertical Electrical Sounding 25
Sample Description: Fine to medium brown sand
with 0-10% silt
Sample Classification: SP |
|
Moisture Content, % |
5.5 |
|
Dry Density, gr/cm3 |
1.94 |
|
pH |
7.7 |
|
Chloride, CL |
18,000 ppm |
|
Sulfate, SO4 |
9,000 ppm |
|
Sulfide, S |
100 ppm |
|
Calcium, Ca |
37,400 ppm |
|
Sodium, Na |
27,600 ppm |
|
Field resistivity, dry |
200 ohm-meter |
|
Lab resistivity, wet |
0.4 ohm-meter |
|
Lab resistivity, dry |
13 ohm-meter |
|
Sample Number: 2
Location: Vertical Electrical Sounding 21
Sample Description: Fine to medium brown sand
with 0-10% silt
Sample Classification: SP
|
|
Moisture Content, % |
5.5 |
|
Dry Density, gr/cm3 |
1.93 |
|
pH |
7.8 |
|
Chloride, CL |
60,000 ppm |
|
Sulfate, SO4 |
15,000 ppm |
|
Sulfide, S |
100 ppm |
|
Calcium, Ca |
47,400 ppm |
|
Sodium, Na |
35,000 ppm |
|
Field resistivity, dry |
1.0 ohm-meter |
|
Lab resistivity, wet |
0.77 ohm-meter |
|
Lab resistivity, dry |
20 ohm-meter |
|
Sample Number: 3
Location: Vertical Electrical Sounding 2
Sample Description: Fine to medium brown sand
with 0-10% silt
Sample Classification: SP
|
|
Moisture Content, % |
9.2 |
|
Dry Density, gr/cm3 |
1.93 |
|
pH |
7.8 |
|
Chloride, CL |
29,000 ppm |
|
Sulfate, SO4 |
12,000 ppm |
|
Sulfide, S |
100 ppm |
|
Calcium, Ca |
47,000 ppm |
|
Sodium, Na |
30,400 ppm |
|
Field resistivity, dry |
50.0 ohm-meter |
|
Lab resistivity, wet |
0.76 ohm-meter |
|
Lab resistivity, dry |
23.5 ohm-meter |


BIBLIOGRAPHY
(1) Beezley, H. V. and Olson,
G. R., 1957, A Collection of Papers on Underground
Pipeline Corrosion, Reprinted from the Petroleum
Engineer, May and June 1957.
(2) CP 1021, 1973, Code of
Practice for Cathodic Protection, British Standards Institution, London, England.
(3) Morgan, John, H., 1960,
Cathodic Protection, Its Theory and Practice in the
Prevention of Corrosion, The MacMillan Company, New
York.
(4) Orellana, Ernesto and
Mooney, Harold M., 1966, Master Tables and Curves
for Vertical Electrical Sounding Over Layered
Structures, Interciencia, Madrid, Spain.
(5) Rosenquist, I., Th., 1961,
Subsoil Corrosion of’Steel, Norwegian Geotechnical
Institute Publication No. 42.
(6) Tagg, C. F., 1964, Earth
Resistances, Pitman Publishing Company, New York.
(7) Van Norstrand, Robert G.
and Cook, Kenneth L., 1966, Interpretation of
Resistivity Data, United States Geological Survey
Professional Paper 499, United States Government
Printing office, Washington, D.C.
|